第2页 CAP 311S AIR POLLUTION CONTROL (PETROL FILLING STATIONS) (VAPOUR RECOVERY) REGULATION

[接上页]

  (a) the Authority shall-
  
  (i) register the certificate by entering particulars of the certificate in a register kept by him for the purpose;
  
  (ii) keep the drawing in the register;
  
  (iii) endorse on the certificate that it has been registered; and
  
  (iv) deliver the certificate as so endorsed to the competent examiner;(b) the competent examiner shall issue the certificate to the owner of the regulated vehicle or petrol filling station to which the certificate relates within 14 days after the receipt of the certificate from the Authority.
  
  Cap 311S s 6 Display of certificate
  
  (1) The owner of a regulated vehicle or petrol filling station shall display the latest certificate showing his compliance with the requirements on testing and examination under section 4 at a conspicuous location on the vehicle or in the station, as the case may be.
  
  (2) The owner of a petrol filling station shall not carry out, or cause or permit to be carried out, any unloading of petrol from a regulated vehicle to a petrol storage tank in the station unless there are the latest certificates displayed in respect of the vehicle and the station.
  
  Cap 311S s 7 Operation
  
  (1) An operator shall not carry out, or continue to carry out, the unloading of petrol from a regulated vehicle to a petrol storage tank if the vapour and liquid connections of the vapour recovery systems of the vehicle and the tank are not completely interconnected.
  
  (2) Where any leakage of petrol occurs during the unloading of petrol from a regulated vehicle to a petrol storage tank, the operator shall stop the unloading as soon as is practicable and not recommence the unloading until satisfied that there will be no further leakage of petrol.
  
  Cap 311S s 8 Exemptions
  
  This Regulation shall not apply to an existing regulated vehicle or existing petrol filling station until the expiration of 12 months immediately following the relevant date.
  
  Cap 311S s 9 Offences and penalties
  
  (1) A person who contravenes section 3(1), or the owner of a regulated vehicle who contravenes section 4(1), commits an offence and is liable on conviction to a fine of $200000 and to imprisonment for 6 months.
  
  (2) A person who contravenes section 3(2), or the owner of a petrol filling station who contravenes section 4(1) or 6(2), commits an offence and is liable on conviction to a fine of $200000 and to imprisonment for 6 months.
  
  (3) The owner of a regulated vehicle who contravenes section 6(1), or the owner of a petrol filling station who contravenes section 6(1), commits an offence and is liable on conviction to a fine at level 5.
  
  (4) An operator who contravenes section 7(1) or (2) commits an offence and is liable-
  
  (a) on a first conviction, to a fine at level 5;
  
  (b) on a second or subsequent conviction, to a fine at level 5 and to imprisonment for 3 months.
  
  Cap 311S s 10 (Omitted as spent)
  
  (Omitted as spent)
  
  Cap 311S Sched 1 STATIC PRESSURE PERFORMANCE TEST FOR THE VAPOUR RECOVERY SYSTEM OF A REGULATED VEHICLE
  
  [sections 3 & 4]
  
  1. General
  
  This procedure applies to the determination of the five-minute static pressure performance of a vapour recovery system of a regulated vehicle by fluid mechanical principles.
  
  2. Determination of compliance
  
  2.1 The outlet of any vent pipe serving the vapour recovery system shall be fitted with a pressure/vacuum valve.
  
  2.2 For tests in sections 5.1 and 5.2, the following requirements shall be complied with the maximum allowable pressure change in 5 minutes for the petrol delivery tank of a regulated vehicle shall be as tabulated below which has been-
  
  (a) pressurized to 4.48 kPa (457 mm water column, gauge); or(b) evacuated to -1.49 kPa (152 mm water column, gauge vacuum).
  
  Capacity of a petrol
  
  delivery tank or a
  
  compartment
  
  (litres)
  
  Allowable pressure change in
  
  5 minutes per petrol delivery
  
  tank or compartment tested
  
  (kPa (mm water column, gauge))
  
  9475 or more
  
  0.127 (13)
  
  5685 to 9474
  
  0.186 (19)
  
  3790 to 5684
  
  0.245 (25)
  
  3789 or less
  
  0.314 (32)
  
  2.3 For tests in section 5.3, the maximum allowable pressure change in the vapour return line in 5 minutes (difference between initial and final pressures) shall be 1.25 kPa (127 mm water column, gauge).
  
  3. Principle and summary of test procedure
  
  The regulated vehicle is to be tested in a location where it will be protected from direct sunlight. The petrol delivery tank on the regulated vehicle is to be pressurized, isolated from the pressure source, and the pressure drop recorded to determine the rate of pressure change. A vacuum test is to be conducted in the same manner.
  
  4. Test equipment
  
  4.1 Source of air or inert gas capable of pressurizing tanks to 6.9 kPa (704 mm water column, gauge).
  
  4.2 Low pressure (1.25 kPa (127 mm water column, gauge) divisions) regulator for controlling pressurization of tank.
  
  4.3 Water manometer with 0 to 6.22 kPa (0 to 635 mm water column, gauge) range, with scale reading of 0.01 kPa (1 mm water column, gauge).
  
  4.4 Test cap for vapour line with a shut-off valve for connection to the pressure and vacuum supply hoses. The test cap is to be equipped with a tap for connecting the manometer.