[接上页] (16) The Director of Electrical and Mechanical Services shall be entitled to enter at all times any of the generating stations or sub-stations of the company supplying or supplied at an extra high pressure, and to make any such examination and tests of the mains, machines, transformers or other apparatus in use in those stations as may appear to him necessary, and the company shall afford all due facilities for any such examination and tests. (L.N. 76 of 1982; L.N. 298 of 1982) (17) Where any extra high pressure circuit is connected with earth the connection shall be made at one point only, namely at the generating station, sub-station or transformer, and the insulation of the circuit shall, except at that point, be efficiently maintained throughout. (18) (a) The neutral point of the star winding of each distinct three-phase circuit, used for extra high pressure, may be connected with earth or may be insulated. If connected with earth through a resistance, that resistance shall be sufficiently low to ensure that the fuse or automatic circuit-breaker in the mains shall act. (b) If the neutral point is not connected with earth a separate electro-static voltmeter placed in a conspicuous position in the generating station shall be connected between each circuit and earth; and if the indications of the voltmeters show that the insulation of any of the circuits is faulty, immediate steps shall be taken to restore the insulation. Cap 406A reg 40 Penalties for default PENALTIES (1) If the company makes default in complying with any of these regulations, it shall be liable to a penalty of $100 for every such default and in the case of continuing offence to a further penalty of $100 for each day during which the offence continues. (2) The recovery of a penalty under these regulations shall not affect the liability of the company to make compensation in respect of any damage or injury which may be caused by reason of the default. Cap 406A reg 41 (Repealed) EXEMPTIONS (Repealed L.N. 215 of 1990) Cap 406A reg 42 (Repealed) (Repealed L.N. 215 of 1990) Cap 406A reg 43 Citation CITATION These regulations may be cited as the Electricity Supply Regulations. |