第4页 CAP 102A WATERWORKS REGULATIONS

[接上页]

  (1) Subject to regulation 25, every pipe or fitting shall be of the British Standard.
  
  (2) Subregulation (1) shall apply only to so much of any British Standard as relates to the size, nature, materials, strength, test requirements and workmanship of any pipe or fitting and shall be deemed to be satisfied notwithstanding any departure from such British Standard if that departure does not in the opinion of the Water Authority adversely affect the efficiency or suitability of the pipe or fitting for the purposes of these regulations.
  
  (3) The Water Authority may at any time weigh, measure or otherwise test any pipe or fitting to ascertain that it complies with the British Standard.
  
  Cap 102A reg 21 Testing of pipes and fittings
  
  (1) The Water Authority may require any pipe or fitting, before it is installed or used, to be tested.
  
  (2) A pipe or fitting which is required to be tested under subregulation (1) shall be delivered to the place specified by the Water Authority and the cost of the testing shall be payable by the person by whom, or on whose behalf, the pipe or fitting is so delivered.
  
  (L.N. 320 of 1992)
  
  Cap 102A reg 22 Protection of pipes
  
  A pipe made of steel if laid under the ground shall be installed in such a manner that it does not come into contact with concrete, cement mortar, lime mortar or plaster and shall be protected against such contact by wrapping it with hessian or other suitable material and coating it with bitumen or where such pipe passes through a wall or suspended floor it may be protected against such contact by being carried through a sleeve or by some other suitable means.
  
  (L.N. 320 of 1992)
  
  Cap 102A reg 23 Booster pumps
  
  (1) Except with the permission in writing of the Water Authority, no person shall install or use a booster pump on a fire service or inside service.
  
  (2) A booster pump shall not pump water direct from a main but from a sump installed at a level at which it can be supplied with water from a main by gravity. (L.N. 252 of 1977)
  
  Cap 102A reg 24 Other water using apparatus
  
  An apparatus using water in respect of which no express provision is made in these regulations or an apparatus for the treatment or filtration of water shall not be installed or used without the permission in writing of the Water Authority and he may require any such apparatus to be supplied with water from a separate storage cistern.
  
  Cap 102A reg 25 Power to relax regulations
  
  (1) The Water Authority may, either generally or in any particular case, relax the provisions of these regulations regarding the size, nature, materials or disposition of any pipe or fitting.
  
  (2) The Water Authority may approve any pipe or fitting which is not of the British Standard.
  
  (3) Where water is-
  
  (a) supplied through a meter;
  
  (b) discharged into a cistern from a point not less than 150 mm above the overflowing level thereof; and (L.N. 252 of 1977)
  
  (c) conveyed therefrom for use in some industrial or research process and is used solely in connection therewith, the Water Authority may exercise his powers under subregulation (1) with regard to any pipe or fitting installed or used for such purpose.
  
  Cap 102A reg 26 Installation of meters
  
  PART IV
  
  METERS
  
  (1) The Water Authority shall determine the size and the number of meters which shall be installed on any fire service or inside service.
  
  (2) Subject to subregulation (2A), all meters shall be provided by the Water Authority. (L.N. 320 of 1992)
  
  (2A) Where a meter is to be installed on a fire service or inside service, the Water Authority-
  
  (a) if he wishes to do so, may, on payment of the charge prescribed in Part I of Schedule 1, provide and install a meter; or
  
  (b) if he does not so wish, shall, on payment of the charge prescribed in Part I of Schedule 1, provide a meter and allow it to be installed by a licensed plumber in such manner as the Water Authority may specify. (L.N. 320 of 1992) (2B) Where a meter is installed otherwise than by the Water Authority, he may refuse to connect the supply until the installation has been inspected and approved by him. (L.N. 320 of 1992)
  
  (3) If the seal fixed on a meter by the Water Authority is broken by any person other than the Water Authority or any person authorized by him it shall be replaced by the Water Authority and the consumer responsible for the custody of the meter shall be liable to pay the charge prescribed in Part I of Schedule 1.
  
  (4) No consumer shall permit any meter to be removed from a fire service or inside service unless the person seeking to remove such meter presents to the consumer a written authority from the Water Authority authorizing him to remove such meter.
  
  (5) The Water Authority may change a meter at any time.
  
  Cap 102A reg 27 Site of meters
  
  (1) The siting of a meter shall be determined by the Water Authority and he may install the meter at a point most convenient to him on any wall (internally or externally) of a building in which there is a fire service or inside service.