第7页 CAP 123I BUILDING (STANDARDS OF SANITARY FITMENTS, PLUMBING, DRAINAGE WORKS AND LATRINES) REGULATIONS

[接上页]

  (c) discharge in a conspicuous position.
  
  Cap 123I reg 24 Traps for soil fitments
  
  (1) Every soil fitment shall be provided with a suitable trap with a water seal of not less than 50 mm.
  
  (2) The internal diameter of every such trap shall be not less than-
  
  (a) 80 mm, in the case of a watercloset fitment, slop sink, or urinal with more than 3 basins or stalls or with a channel longer than 2 m;
  
  (b) 50 mm, in the case of a urinal with more than one and not more than 3 basins or stalls or with a channel not longer than 2m;
  
  (c) 40mm, in the case of a bidet or urinal with a single basin or stall; and
  
  (d) 100 mm, in the case of a trough watercloset.
  
  (L.N. 294 of 1976)
  
  Cap 123I reg 25 Traps for waste fitments
  
  (1) Every waste fitment shall be provided immediately under the fitment with a suitable trap:
  
  Provided that a trap shall not be required-
  
  (a) where the waste pipe from such fitment-
  
  (i) does not exceed 1 m in length; and
  
  (ii) discharges over or into a suitable trapped gully;(b) in respect of lavatory basins, where the waste pipes therefrom discharge in the manner provided by regulation 12(2);
  
  (c) in respect of a range of shower baths, where the drainage channel provided therefor is provided, at its lowest point, with a trap.(2) Save as provided in paragraph (3), every trap provided for a waste fitment shall have-
  
  (a) an internal diameter of not less than 32 mm; and
  
  (b) a water seal of not less than 40 mm.(3) Where the waste pipe from a waste fitment is, under the provisions of regulation 12(3), connected to a soil pipe, the trap provided for the waste fitment shall-
  
  (a) have an internal diameter of not less than 32 mm;
  
  (b) have a water seal of not less than 80 mm; and
  
  (c) be-
  
  (i) adequately ventilated; or
  
  (ii) constructed to prevent loss of water seal.
  
  (L.N. 294 of 1976)
  
  Cap 123I reg 26 Soil pipes
  
  Pipes and eaves gutters
  
  (1) The internal diameter of every soil pipe from a watercloset fitment or slop sink shall be not less than-
  
  (a) 80 mm; or (L.N. 294 of 1976)
  
  (b) the internal diameter of the outlet pipe of the trap of any fitment to which the soil pipe is connected,whichever is the greater.
  
  (2) The internal diameter of every soil pipe from a urinal or bidet shall be not less than the internal diameter of the outlet pipe of the trap of any fitment to which the soil pipe is connected.
  
  (3) Every soil pipe shall be properly connected to a covered drain without the intervention of any trap.
  
  Cap 123I reg 27 Waste pipes
  
  (1) Waste pipes to which the waste from one waste fitment is discharge shall have an internal diameter of not less than-
  
  (a) 32 mm; or (L.N. 294 of 1976)
  
  (b) the internal diameter of the outlet of the trap to which the waste pipe is connected,whichever is the greater.
  
  (2) Waste pipes to which the waste from more than one fitment is discharged shall be of adequate diameter to convey all such waste.
  
  (3) Every waste pipe shall terminate at its lower end not more than 150 mm above the channel or trapped gully over or into which it discharges. (L.N. 294 of 1976)
  
  Cap 123I reg 28 Bends in soil and waste pipes
  
  (1) Soil pipes and waste pipes shall not have bends therein, except where unavoidable.
  
  (2) Whenever a bend is unavoidable-
  
  (a) the bend shall-
  
  (i) have an obtuse angle;
  
  (ii) have the largest practicable radius of curvature; and
  
  (iii) not change in any way the cross section of the pipe;and(b) a cleaning eye or other suitable means of access shall be provided at or near the bend.
  
  Cap 123I reg 29 Access to soil and waste pipes
  
  (1) Sufficient access shall be provided, by means of cleaning eyes or other approved method, to enable soil pipes and waste pipes to be cleared of any obstruction.
  
  (2) Such access points shall be so sited as to allow clearance for the easy entry of cleaning rods.
  
  Cap 123I reg 30 Anti-syphonage pipes
  
  (1) Where-
  
  (a) more than one trap of a watercloset fitment, urinal, slop sink or waste fitment is connected with one soil pipe; or
  
  (b) more than one trap of a waste fitment is connected with one waste pipe,the traps shall be ventilated by means of anti-syphonage pipes:
  
  Provided that if, in the case of waste fitments, the traps to such fitments are constructed to prevent loss of water seal, it shall not be necessary to provide an anti-syphonage pipe, unless the Building Authority so requires.
  
  (2) Every anti-syphonage pipe shall be connected with-
  
  (a) the trap, if the connection with the anti-syphonage pipe is an integral part of the trap; or
  
  (b) the branch soil pipe or branch waste pipe-
  
  (i) on the side of the water seal nearest the main soil pipe or waste pipe; and
  
  (ii) at a point not more than 300 mm from the trap outlet. (L.N. 294 of 1976)(3) The internal diameter of every anti-syphonage pipe shall-
  
  (a) if the diameter of the soil pipe or waste pipe to which it is connected is 80 mm or more, be not less than 50 mm;
  
  (b) if the diameter of such soil pipe or waste pipe is less than 80 mm, be not less than-
  
  (i) two-thirds of the internal diameter of such soil pipe or waste pipe; or