CAP 132CE VENTILATION OF SCHEDULED PREMISES REGULATION


  VENTILATION OF SCHEDULED PREMISES REGULATION
  
  (78 of 1999 s. 7)
  
  (Cap 132, section 94A)
  
  [26 November 1977]
  
  (L.N. 260 of 1977)
  
  Cap 132CE s 1 (Repealed 78 of 1999 s. 7)
  
  Cap 132CE s 2 (Repealed 78 of 1999 s. 7)
  
  Cap 132CE s 3 Interpretation
  
  In this Regulation, unless the context otherwise requires- (78 of 1999 s. 7)
  
  "licensing authority" (发牌当局) has the meaning assigned in section 93(5) of the Ordinance.
  
  (78 of 1999 s. 7)
  
  Cap 132CE s 4 Requirements with respect to ventilating systems
  
  (1) Save as provided in subsection (2) and section 101 of the Ordinance, every ventilating system in any scheduled premises shall comply with the following provisions-
  
  (a) all moving parts thereof shall be securely fenced;
  
  (b) every part thereof shall be accessible for the purposes of inspection, and, in particular-
  
  (i) the spindle of every fan shall be so sited that its guard may be removed and a tachometer applied thereto; and
  
  (ii) every air intake and exhaust shall be accessible for the purposes of measurement; (c) no air intake for the ventilating system shall be sited in any place -
  
  (i) which constitutes a fire hazard in the opinion of the Director of Fire Services;
  
  (ii) where waste or rubbish is likely to accumulate; or
  
  (iii) where the air is for any reason impure or likely to become impure;(d) the opening of every air intake shall be fitted with a screen constructed of corrosion-resistant material having a mesh not greater than 12 mm;
  
  (e) an air intake damper shall be-
  
  (i) adjusted to a setting approved by the Director of Food and Environmental Hygiene;
  
  (ii) marked indelibly to indicate the approved setting; and
  
  (iii) secured against interference; (f) no exhaust from the ventilating system shall be sited in any place where it causes, or is likely to cause, annoyance or inconvenience to the public;
  
  (g) every duct shall-
  
  (i) be wholly constructed of non-combustible material having a strength and durability similar to that of galvanized sheet iron or steel;
  
  (ii) be accessible for the purposes of cleaning throughout its entire length;
  
  (iii) where its size is sufficient to allow any person to enter therein, be fitted with access openings to allow a person to enter the same for the purpose of cleaning, and shall be constructed to bear the weight of any person who has so entered;
  
  (iv) be provided with a smooth and impervious internal surface;
  
  (v) where it passes through any floor, wall or ceiling, be fitted with a damper which shall be operated by fusible links of a type approved by the Director of Fire Services, and designed to operate up to a temperature of 69 degrees Celsius, and be so constructed or protected as to resist the action of fire for a period not less than the period for which the floor, wall or ceiling through which it passes is designed to resist the action of fire; (L.N. 301 of 1982) (h) no duct shall serve more than one building;
  
  (i) an air filter shall be-
  
  (i) constructed wholly of non-combustible material, other than steel wool;
  
  (ii) of a design approved by the Director of Food and Environmental Hygiene; and
  
  (iii) installed in such manner that all incoming air passes through it before being distributed within the premises; (j) every electrostatic filter or precipitator shall be of a type approved by the Director of Fire Services;
  
  (k) every blower fan shall be fitted with a fused running hour meter connected to the load side of the fan contractor with a device for recording time in minutes and hours or tenths or lesser fractions of an hour;
  
  (l) each fused running hour meter shall be sited in an easily accessible and conspicuous place to facilitate inspection;
  
  (m) each set of filters in a ventilating system shall be indicated by a filter gauge, filter flag indicator or differential pressure switch;
  
  (n) filters shall be cleaned or replaced when the filter gauge, filter flag indicator or differential pressure switch shows an increase of 50 pascals over the designed air filter pressure drop; and
  
  (o) a filter flag indicator shall indicate "dirty" when there is an increase of 50 pascals over the designed air filter pressure drop. (2) Where he thinks fit and subject to such conditions as he may specify, the Director of Food and Environmental Hygiene may exempt any ventilating system in respect of which application in writing in that behalf is made from compliance with all or any of the requirements of subsection (1).
  
  (78 of 1999 s. 7)
  
  Cap 132CE s 5 Ventilating system to be kept in operation, etc.
  
  (1) Every ventilating system provided pursuant to the requirements of a notice given under the provisions of subsection (1) or (2) of section 93 of the Ordinance shall, at all times when the premises for which it is provided are open to the public, be kept in operation so as to provide, respectively, the amount of outside air required to be provided by the provisions of subsection (1) or the notice given under the provisions of subsection (2).
  
  (2) Every ventilating system provided in any scheduled premises otherwise than pursuant to the requirements of a notice given under the provisions of subsection (1) or (2) of section 93 of the Ordinance shall, at all times when the premises are open to the public, be kept fully in operation.