CAP 406A ELECTRICITY SUPPLY REGULATIONS


  (Cap 406, section 59(1))*
  
  [19 May 1911]
  
  (18 of 1911 Schedule)
  
  _________________________________________________________________________________
  
  Note:
  
  * These regulations were made under section 3 of the repealed Electricity Supply Ordinance (Cap 103, 1976 Ed.). See section 36(1) of the Interpretation and General Clauses Ordinance (Cap 1) and section 59(1) of the Electricity Ordinance, enacted in 1990 (Cap 406).
  
  Cap 406A reg 1 Interpretation
  
  DEFINITIONS
  
  (1) In these regulations, unless the context otherwise requires-
  
  "company" (公司) means any person or any body of persons corporate or unincorporate by whom electricity is generated or supplied; (L.N. 215 of 1990)
  
  "consumer's wires" (用户电线) means any electric lines which are connected to the service lines of the company at the company's meter terminals; (L.N. 138 of 1976)
  
  "electricity" (电力) means electricity, electric current or any like agency; (L.N. 215 of 1990)
  
  "overhead line" (架空电缆) means any electric line which is placed above ground and in the open air;
  
  "pressure" (压力) means the difference of electrical potential between any 2 conductors through which a supply of energy is given, or between any part of either conductor and the earth; and-
  
  (a) where the conditions of the supply are such that the pressure at any pair of consumer's terminals does not exceed 250 volts, the supply shall be deemed a low pressure supply;
  
  (b) where the conditions of the supply are such that the pressure exceeds 250 volts but does not exceed 650 volts, the supply shall be deemed a medium pressure supply;
  
  (c) where the conditions of the supply are such that the pressure exceeds 650 volts but does not exceed 3000 volts, the supply shall be deemed a high pressure supply; and
  
  (d) where the conditions of the supply are such that the pressure exceeds 3000 volts, the supply shall be deemed an extra high pressure supply;"street" (街道) includes any square, court or alley, highway, lane, road, thoroughfare or public passage or place; (L.N. 215 of 1990)
  
  "sub-station" (电力分站) means any premises in which energy is transformed or converted for the purpose of supply to consumers, and which are large enough to admit the entrance of a person after the transforming or converting apparatus is in position:
  
  Provided that for the purpose of these regulations any place within any such premises which is used solely for some purpose other than such transformation or conversion shall not be deemed to form part of a sub-station;"works" (工程) includes electric lines and any buildings, machinery, engines, works, matters or things of whatever description required to supply electricity and to carry into effect the objects of a company. (L.N. 215 of 1990)
  
  (69 of 1999 s. 5)(2) Where these regulations require any metallic body to be "efficiently connected with earth", it shall be connected with the general mass of earth in such manner as will ensure at all times an immediate and safe discharge of electrical energy.
  
  Cap 406A reg 2 Pressure of supply to consumers
  
  Remarks:
  
  Adaptation amendments retroactively made - see 61 of 2000 s. 3
  
  GENERAL
  
  The pressure of a supply delivered to any consumer shall not exceed the limit of low pressure except for special purposes, for which a medium pressure supply may be given on the consumer undertaking to comply with the following conditions-
  
  (a) where the supply is for power purposes-
  
  (i) the frame of every electric motor shall be efficiently connected with earth;
  
  (ii) the consumer's wires forming the connections to motors, or otherwise in connection with the supply, shall be, as far as practicable, completely inclosed in strong metal casing efficiently connected with earth, or they shall be fixed in such a manner that there shall be no danger of any shock;
  
  (iii) the supply to every motor shall be controlled by means of an efficient cut-off switch, placed in such a position as to be easily handled by the person in charge of the motor, and connected so that by its means all pressure can be cut-off from the motor itself and from any regulating switch, resistance or other device in connection therewith;
  
  (iv) switches, efficient fuses or other automatic circuit-breakers shall be provided, so as to protect the circuits from excess of current, and all switches and cut-outs shall be so inclosed and protected that there shall be no danger of any shock being obtained in the ordinary handling thereof, or of any fire being caused by their normal or abnormal action;
  
  (v) a notice shall be fixed in a conspicuous position at every motor and switch board in connection with the supply forbidding unauthorized persons to touch the motors or apparatus;(b) where the supply is for arc lamps in series-
  
  (i) the consumer's wires forming the connections to the arc lamps, or otherwise a connection with the supply, shall be, as far as practicable, completely inclosed in strong metal casing efficiently connected with earth, or they shall be fixed in such a manner that there shall be no danger of any shock;