第6页 CAP 470 BUILDERS' LIFTS AND TOWER WORKING PLATFORMS (SAFETY) ORDINANCE

[接上页]

  (a) examination of all machinery and equipment to ensure it is in good working condition;
  
  (b) functional tests at rated speed and at rated load;
  
  (c) testing of driving machine brake, and additional braking system, if any, at 125% of rated load and at rated speed;
  
  (d) testing of overload sensing device at not more than 110% of rated load;
  
  (e) testing of safety gear at rated load and at tripping speed of the overspeed governor.
  
  (Enacted 1995)
  
  Cap 470 s 19 Report and certificate of registered examiner after installation or major alteration
  
  (1) Where a registered examiner, after carrying out the test and examination, is satisfied that a builder's lift or tower working platform, as the case may be, complies with the relevant requirements set out in section 9 and is in safe working order, he shall forthwith deliver to the registered contractor, in the form and containing the information specified by the Director-
  
  (a) a report on the test and examination; and
  
  (b) a certificate of test and examination in duplicate.(2) The registered contractor shall forthwith countersign the certificate and deliver it and the report to the owner.
  
  (3) The owner shall deliver the report and certificate to the Director together with the prescribed fee, and the Director shall, if he is-
  
  (a) satisfied with the report and certificate, endorse the original of the certificate and return it to the owner; or
  
  (b) not satisfied with the report and certificate, notify the owner in writing that the use of the builder's lift or tower working platform, as the case may be, is prohibited, and the Director shall give his reasons for prohibiting its use.(4) Where the registered examiner is not satisfied that the builder's lift or tower working platform, as the case may be, complies with the relevant requirements set out in section 9 or is not in safe working order, he shall immediately report that fact to the Director and the registered contractor, and the registered contractor shall take the necessary steps to correct the problem.
  
  (5) When the registered contractor has taken the necessary steps to correct the problem, the registered examiner shall carry out a further test and examination under this section.
  
  (6) The owner shall ensure that a builder's lift or tower working platform to which this section applies is not used until he receives the endorsed original of the certificate from the Director under subsection (3)(a).
  
  (Enacted 1995)
  
  Cap 470 s 20 Report of registered examiner after alteration of height of travel
  
  (1) Where a registered contractor carries out lift work that alters the height of travel of a lift cage or platform, he shall, before allowing it to be used, employ a registered examiner to carry out a test and examination of the builder's lift or tower working platform, as the case may be.
  
  (2) In this section, "test and examination" (测试及检验) means carrying out the following safety checks-
  
  (a) examination of all machinery and equipment to ensure it is in good working condition;
  
  (b) checking the condition of the mast extension and its anchorage to adjacent structure;
  
  (c) checking the condition of the suspension system including the rack and pinion suspension system or rope suspension system;
  
  (d) checking the operation of the safety gear;
  
  (e) checking the operation of other safety devices including final limit switches and the electro-mechanical interlocking devices;
  
  (f) testing the running of the lift cage or platform, as the case may be, over the full range of normal operating travel.(3) Where the registered examiner, after carrying out the test and examination, is satisfied that the builder's lift or tower working platform, as the case may be, complies with the relevant requirements set out in section 9 and is in safe working order, he shall forthwith deliver to the registered contractor a report on the test and examination in the form and containing the information specified by the Director.
  
  (4) The registered contractor shall attach the report to the log book required to be kept under section 21 and shall make the report available to the Director on request.
  
  (5) Where the registered examiner is not satisfied that the builder's lift or tower working platform, as the case may be, complies with the relevant requirements set out in section 9 or is not in safe working order, he shall immediately report that fact to the Director and the registered contractor, and the registered contractor shall take the necessary steps to correct the problem.
  
  (6) When the registered contractor has taken the necessary steps to correct the problem, the registered examiner shall carry out a further test and examination under this section and, if satisfied, shall advise the Director of that fact.
  
  (7) The owner shall ensure that a builder's lift or tower working platform to which this section applies is not used until he is advised by the registered contractor that the report has been received from the registered examiner.
  
  (Enacted 1995)